Surge arrester for Loxone LINK bus

 

  • For new and existing systems (can be retrofitted)
  • Simple installation (no complex wiring required, mounting on DIN rail, simple plug-in system)
  • No defective devices in the event of overvoltage or short circuit (no expensive repair costs)
  • Increase in reliability and system availability
  • DIN rail mounting
  • Certified in a recognized testing institute

 

  • For new and existing systems (can be retrofitted)
  • Simple installation (no complex wiring required, mounting on DIN rail, simple plug-in system)
  • No defective devices in the event of overvoltage or short circuit (no expensive repair costs)
  • Increase in reliability and system availability
  • DIN rail mounting
  • Certified in a recognized testing institute

 

FOR ALL CAN BUS SYSTEMS SUCH AS LOXONE LINK AND LOXONE TREE

 

operating range

  • Nominal voltage / maximum continuous voltage D+ to GND: -7V to +14V
  • Nominal voltage / maximum continuous voltage D- against GND: -7V to +14V
  • Leakage current D+ to GND:  < 1.5µA
  • Leakage current D- to GND:  <1.5µA
  • Leakage current D+ to D-:  < 1µA
  • Insulation resistance at nominal voltage: > 6 MOhm
  • Capacitance D+ to GND: 75 pF
  • Capacitance D- to GND: 75 pF
     

Protection level (at overvoltage 10,000 V and 5,000 amperes)

  • Data lines, D+ to GND: < 620 V (with pulse class C2, 10,000 V (1.2/50 µs) / 5,000 A (8/20 µs)
  • Data lines, D- to GND: < 606 V (with pulse class C2, 10,000 V (1.2/50 µs) / 5,000 A (8/20 µs)
  • current limit: The remaining harmful current from the protection level is switched off after 1 µs by current cut
  • Pulse recovery, D+ to GND: <0.74 ms (measured at 2000 V (1.2/50 µs) / 1,000 A (8/20 µs)
  • Pulse recovery, D- to GND: <0.85 ms (measured at 2000 V (1.2/50 µs) / 1,000 A (8/20 µs)

LOX SHIELD LINK